Battery Monitoring System including:

Intelligent Gateway

Built-in embedded software, One per UPS, Max. Monitor 4 Strings

Battery String Sensor

One per String, each string max 120 pcs batteries)

Battery Cell Sensor

Battery String Sensor

Feature

  • 24/7 Hours On-line Monitoring & Remote Alarms Notification
  • Suitable for UPS and Data Center Application
  • Anti-interference Design, Support to Connect with High-frequency UPS
  • Build-in Web Server with Visual Display
  • Provide HMI for Local Display
  • On-line Balancing Function
  • On-line Remote Firmware Upload
  • Support Auto-Sensing for the Battery Sensor’s ID Address
  • Support Multi-Communication Protocol(MODBUS-TCP,SNMP)
  • Apply with IEEE 1188-2005 Standard

System Structure

Intelligent Gateway

  • Real-time monitoring 1 UPS with Max. 480 batteries
  • Data logging for all measuring data for 12 months
  • Build-in web server with bar chat and trend curve analysis for Voltage,Charge and discharge current, Internal Temperature, Impedance
  • Auto-Balancing Function
  • Report for battery string voltage & current, individual battery voltage,temperature, impedance,support export PDF,.CSV etc.document
  • Setpoint alarm for Cell Voltage, Internal Temperature, Impedance, SOC,SOH (High limit / lower limit)
  • Setpoint alarm for String Voltage, Current, SOC (High limit / lower limit)
  • Monitor Ambient Temperature & Humidity (Optional)
  • DO for sound and light alarm (Optional)
  • DI for digital Input connect (Optional)
  • Support SNMP,Modbus TCP protocol
  • Support SMS alarm

Battery String Sensor

  • Monitor Battery String Voltage, Charge and Discharge Current
  • Calculate Battery State Of Charge (SOc)
  • Auto Balancing function
  • Data Collecting function
  • Auto-sensing for Whole Battery String Sensor’s lD address
  • Asssorries:
    1) Hall Sensor and Cable: Range from 0~+1000A with 2m cable
    2) Communication Cable : 5m with RJ11 port


Running Status

Alarm Status

Hall Sensor

External Power SupplyMeasuring Range
VoltageString CurrentPower Consumption
Measuring Range20V to 800V(士0.5%)-1000A~ +1000A (By Hall sensor)(±2.0%)1W

Dimension and Installation

Battery Cell Sensor

  • 7″ inch Touch-Screen HMl for Data Display and Operation
  • Real-time Data Inquiry
    1) Individual Battery Voltage, Impedance, Internal Temperature,SoC, SOH
    2) String Voltage, Charge and discharge Current, SOC,Balance degree
  • Alarm Data Inquiry
    1) Real-time alarm state and related alarm information (Problem battery ID,Datel Time,Alarm Reason, communication state etc..)
    2)1000 Alarm Records for each string battery
Rated
Input
Measuring Range
VoltageVoltageInternal TemperatureImpedancePower Consumption
2V1.6v to 2.6V (士0.2%)-20℃ to 85℃(土0.5℃)0.1mQ to 100mΩ
Repeatability Error: 1.0%±25uΩ
Conformity Error:1.5%±25uΩ
Runing: <110mW
Sleeping:<12mW
2V7.5V to 15.6V (土0.2%)Runing: <90mW
Sleeping:<10mW

Local Display & Operation Layer (Optional)

  • Monitor Individual Battery Voltage, Internal Temperature (Negative pole),lmpedance(Ohmic Value)
  • Calculate Individual Battery State Of Charge (SOC), State of Health (SOH)
  • Auto-Balancing Function
  • Hot pluggable,3M Adhesive Tape Mounting
  • Accessories:
    1) Battery measuring cable: 30cm
    2) Communication Cable : 40cm & 70cm with RJ11 port (optional)